Need Help? Chat with us

1010– 1500 kAV

7 Easy steps for a happy Genset Ownership

1010 - 1500 kVA TECHNICAL SPECIFICATIONS

Prime Rating at rated RPM (as per ISO 8528) kVA 1010 HD 1250 HD 1500 HD
kW 808 1000 1200
Genset Model KG1-1010WS KG1-1250WS KG1-1500WS
Frequency Hz 50
Power Factor Lagging 0.8
Voltage V 415 (3Ø)
Governing Class (ISO 8528 Part-V) G3
DG Set Noise Level @ 1 Mtr (With Canopy) dBA Contact Kirloskar Oil Engines Ltd for Details
Fuel Tank Capacity (Inbuilt) Ltrs 990 NA
Weight of Genset with Canopy (Approx.) Dry (Kg) 13200 13075+
Overall Dimensions of Genset Length (mm) 7800 5650+
Width (mm) 2300 2300+
Height (mm) 2713 2680+
Electrical Battery Starting Voltage Volts-DC 24

ENGINE

Engine Model (Parent Engine) DV16ETA 12K4300-E1 12K4300-E2
Rated Output (ISO 3046) kW 889 1090 1294
HP 1210 1482 1760
No. of Cylinders Number 16 12 12
Cubic Capacity Ltrs 31.84 51.73 51.73
Bore × Stroke mm 130 × 150 170 × 190 170 × 190
Rated Speed RPM 1500
Aspiration NA / TC / TA TA
Lube Oil Change Period hrs 500
Lube Oil Sump Capacity Ltrs 130 265 265
Coolant Capacity with Radiator Ltrs 180 210 210

ALTERNATOR

Insulation Class Class H
Ingress Protection IP 23
Alternator Efficiency @100% Load (0.8 PF) % 95.1 95.7 95.4
Alternator Efficiency @75% Load (0.8 PF) % 95.4 95.9 95.8
Permissible Voltage Dip at Full Load (0.8 PF Lag) < 20%
Time Permitted to Build-up Rated Voltage @ Rated RPM < 1 sec, provided engine should reach rated RPM
Short Circuit Withstand Time sec 3 Times rated current for “10 sec”
Overload Withstand Capacity % 10% overload for one hour once in 12 hours

Genset kVA 1010 to 1500 kVA Features

‘Prime power’ is designed for Unlimited hours, as compared to ‘Emergency stand-by’ designed for 200 hours in a year. Prime rated Gensets also permit 10% temporary overloading. Users need to carefully select the Genset rating to meet their requirement. Kirloskar offers Prime power as a standard offer. Contact Kirloskarfor stand-by ratings.

  • Engine capacity (cc) plays a vital role in Genset performance. Higher engine capacity leads to arobust and stable Genset performance.
  • Higher engine capacity also enables the Genset torespond quickly & positively to sudden loadadditions.

Kirloskar Green Gensets offer a unique combination of CPCB norm compliance and enhanced fuel efficiency. Across the range, Kirloskar Green Gensets offer substantial savings in fuel cost.

  • Genset ratings are selected based on the present load and future expansion. Fuel efficiency of most Gensets is optimized at the full rating of the Genset.
  • In practice, Gensets rarely get loaded to full capacity. Power demand variations across day & night, weekdays & weekends, summer & winter lead to an average 50-70% loading on Gensets.
  • Considering this practical situation, Kirloskar has extended fuel efficiency optimization from 100%, right up to 50% of rated load.
  • Combination of best-in-class fuel efficiency & O2E provides a double advantage.

Kirloskar Green gensets are enabled with Kirloskar remote monitoring system which shares Real Time Genset information and location Services. It can be accessed via mobile device or desktop. Kirloskar remote monitoring system also highlights any parameter which needs special attention. These critical indication alerts are sent to user mobile via text message. It also alerts nearest services dealer is case of any emergency break-down.

  • Kirloskar Green Gensets have always been preferred for their robust design and reliability over long usage life.
  • Kirloskar Green range carries the confidence of well-established and proven engine platforms. For compliance to revised CPCB norms, Kirloskar has carefully selected those technologies which not only retain, but enhance Gensets durability and on-site serviceability.
  • Thus, Kirloskar Gensets offer you many years of trouble-free performance; backed by the assurance of prompt support. Peace-of-mind driven by product reliability and low cost of ownership.

Kirloskar Green Genset put the command in your hands. Micro-processor based Genset controllers display a host of genset parameters and put all controls at your fingertips.

Monitoring Features

  • Phase Voltages & Currents, Frequency, Reverse power, Genset kVA, kW, kWh, kVAr, Power Factor, Canopy Temperature.
  • Lube oil Pressure, Engine Temperature, RPM, Run Hours, Number of starts, Fuel Level, Auto / Manual Stop, Battery charge condition, AMF feature

Diagnostic Features

  • Battery charging failure, Over/Under speed, Over Current, Over/Under Voltage, Over kW, Phase Seq., Phase missing, Mains Under voltage, Earth Fault trip, Fuel usage Alarm
  • Low lube oil Pressure, High Engine Temperature, Low/High battery voltage, Low Fuel Level, Over Crank protection, Routine maintenance indicator, Genset Test Facility, Mains Frequency

Optional Features

  • Modbus Communication